STUDER 
INNOTEC 
 
      HP-COMPACT 
 
 
 
User manual 
HP-COMPACT V3.0 E 
8  
3.2 Fixing 
3.2.1 HP-COMPACT 
Basically the HP-COMPACT can be installed in any desired location but only vertically. 
First of all the plate supplied along with the HP-COMPACT must be screwed firmly (due to 
the weight of the device) on the wall. Then the HP-COMPACT is hooked on the plate and 
screwed underneath. 
Cautious: the fixing must be fully made otherwise the HP-COMPACT may fall and cause 
important damages. 
In motor vehicles HP-COMPACT must be fixed on vibrations reducing elements. The HP-
COMPACT must not be fixed on a combustible base, as the back of the casing can get hot 
and reach up to 60 degrees Celsius. 
3.3 Connections 
3.3.1  General instructions on connecting 
The cable connection on the terminals AC INPUT and AC OUTPUT must be carried out 
with a screwdriver Nr.3 and the connection of the AUX RELAY terminal with a screwdriver 
Nr.2. 
The conductor cross section on the terminals AC INPUT / AC OUTPUT / must comply with 
the local rules. 
All connecting cables and also the battery cables must be fixed with strain relief clamps. 
The fuses supplied with the HPC4024, 5048 and 7048 have to be installed (see descrip-
tion in 3.4). The cable cross section for the HP 2512, 4024, 5048 and 7048 is resp. 95, 70, 
50 and 70 mm
2
 and their length must be as short as possible (max. 2m). 
The fuse supplied with the product (save for HPC 2512) does not protect the battery ca-
bles. 
To protect the battery cables, a fuse corresponding to the conductor cross section must be 
fixed directly on to the battery. 
All cables must be tightly screwed in place. For safety, a yearly control is recommended. In 
mobile installations controls must be carried out more often. 
Connecting must be done by qualified people. Material such as cable, connectors and dis-
tribution boxes, fuses etc. used in the installation must comply with the respective valid 
low-voltage installation rules and regulations in force. 
3.3.2  Protection cover of the terminals connections 
The protection cover must to be closed after any service on the appliance.