Справочник Пользователя для Studer Innotec C1312 COMPACT

Скачать
Страница из 23
STUDER INNOTEC 
   
                                                        
COMPACT
COMPACT
COMPACT
COMPACT
 
 
User manual 
COMPACT V2.0 E 
15 
 
1.9
 
2.3
 
2.50
 
[V/cell]
 
2.1
 
A
 
B
 
C
 
D
20
60
40
70
[A]
A
B
C
D
t
Equalization
Absorption
Floating
Charging current (adjusted)
 
Charging time
 
Egalization time
 
Absorption time
 
Floating
4.6  The Battery charger 
4.6.1  Cycle of charge 
The full automatic COMPACT Battery Charger is adjusted at the factory so that most lead-acid and 
lead-gel batteries can be charged to the maximum. As soon as the minimum alternating voltage for 
the AC IN set on the Turning Knob 23 is available at the input (LED 1 AC IN is lit), the Battery 
Charger is switched on automatically (LED 2 CHARGER is lit). The battery is fully automatically 
charged matching to the charge level, the adjusted voltage levels and the charge current. Thanks 
to the built-in Float Charge System, the batteries can be left connected for unlimited time with the 
Battery Charger switched on.  
During the charging phase the consuming devices at the outlet AC OUT are continually supplied 
with power (LED 8 AC OUT is lit).  
 
The charger functions are shown in the following diagram: 
4.6.2 Equalization 
charging: 
Before you program the COMPACT for Equalization-charge you must confirm with your supplier 
that the batteries are suitable for this process. 
Equalization is recommended for the lead-acid batteries in order to mix well the electrolyte fluid 
and to clean the lead plates. 
 Equalization mode should never be used when using Gel-Batteries  
If the COMPACT is operating with a lead-acid battery, which is suitable for equalization, the slide 
switch „Equalize“ which is on the cable connection side, must be placed in the ON position. In this 
setting, at every 25 charge cycles an equalization is carried out for 2 hours (factory setting). During 
such a charge cycle the LED 14 is lit. Charge cycle with equalization can be started independently 
of the actual program. For this the slide switch must be slid from “OFF” to the  “ON” position. The 
LED 14 will light up. If the periodic equalization is not required, slide switch must be slid back to the 
„OFF“ position  after the completion of the manual cycle.  
CAUTION:
 During the equalization process, the batteries produce lot more gas.  
DANGER OF AN EXPLOSION !!   
 
4.6.3  Input current repartition (Power sharing) 
For manage the power available on the AC INPUT (depend the supply use) the COMPACT is 
equiped with a system usually called “Power sharing” or INPUT power distribution. With this 
function it’s possible to limit the AC INPUT current assigned to the charger. More current it use on