Caution: No external voltage should be connected to this Input Control. 
4.11 The Temperature sensor 
Operating voltage of lead-acid batteries change depends on the 
temperature. To correct the operating voltages according to the actual 
temperatures, a temperature sensor can be connected to the COMPACT.   
The compensation through the sensor is –3mV/°C/Cell. 
 
Order Number: CT-35 
Dimensions: H x B x T / 58 x 51.5 x 22mm 
5 Programming 
5.1 Standard 
setting 
The COMPACT is delivered with the default setting following: 
5.1.1 Working 
mode 
The working of the charger, the inverter and the transfer are described in chapter 5.3/5.4/5.5. 
5.1.2 Battery 
voltage 
Low voltage 
11.6V / 23.2V / 46.4V 
Float Charge 
13.5V / 27.0V / 54.0V 
End of Charge Voltage 
14.4V / 28.8V / 57.6V 
Equalization 
15.3V / 30.6V / 61.2V 
Absorption Time: 
2 Hours 
5.1.3 Auxiliary 
contact 
Active in case of defect or manual turn off with the LED 10/11/12/13 
5.2 Reset 
value 
When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always 
programmed with these standard settings.  
In order to get to these settings during operation you must press the three Push Buttons 19/20/21 
simultaneously for a minimum of 2 seconds. 
5.3  Battery voltages and absorption time 
The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of 
the absorption charge can be changed.  
The display of these voltages and the times in the program mode are in accordance with the 
diagram shown below: 
 
5.3.1   Table of voltage and timing threshold  
 
 Low 
voltage 
LED 13 
Float Charge 
LED 12 
Absorption 
LED 11 
Equalization 
LED 10 
Absorpt. 
Time 
LED 10->13 
LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V 12/24/48V 
14  12.0 24.0 48.0 13.7 27.4 54.8 16.2 32.4 64.8 16.2 32.4 64.8 4 
15  11.8 23.6 47.2 13.6 27.2 54.4 15.6 31.2 62.4 15.9 31.8 63.6 3 
16  11.6 23.2 46.4 13.5 27.0 54.0 15  30  60  15.6 31.2 62.4 2 
17  11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.3 30.6 61.2 1 
18  11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15  30  60  0 
– 
1Min. 
The heavy printed values show the standard settings.