10
CN51
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor
controller board and relay
must be within 10m (33ft).
Be sure to secure insulation
material by tape, etc.
5
Green
Yellow
Orange
Connector (5P)
Indoor unit side
Multiple remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape, etc.
Installation at site
CN51
on
indoor
controller
board
Red
Brown
1
~
CN51
MB
5-3. OPERATION IN CONJUNCTION WITH 
DUCT FAN (Booster fan)
• Whenever the indoor unit is operating, the duct fan also 
operates.
(1) Connect the optional multiple remote controller adapter 
(PAC-SA88HA-E) to the connector CN51 on the indoor 
controller board.
(2) Drive the relay after connecting the 12V DC relay 
between the Yellow and Orange connector lines.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (For DC 12V, coil rating: 1.0W or smaller)
 Branch duct hole
 14-:1/8 (:2.8) burring hole 
 Indoor unit
:5-29/32 (:150) cut out hole 
 Fresh air intake hole
:6-7/8 (:175) burring hole pitch
 Drain pipe
 Fresh air intake hole diagram
 Unit : inch(mm)
 Refrigerant pipe
 3-:1/8 (:2.8) burring hole 
 Branch duct hole diagram
 (view from either side)
:4-29/32 (:125) burring hole pitch
  3-:15/16 (:100) cut out hole
 Ceiling
6-7/32
(*158)
120
120
13-25/32 (350)
3-17/32
(90)
3-15/16
(100)
3-15/16
(90)
3-17/32
(90)
70
3-15/16 (100)
5-1/8 (130)
*6-3/32 (155)
*6-9/16 (167)
5-2. BRANCH DUCT HOLE AND FRESH AIR INTAKE HOLE
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when 
required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figures marked with * in the drawing below represent the dimensions of the main unit excluding those of the optional 
multi function casement.
When installing the optional multi function casement, add 5-5/16” (135 mm) to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately. 
Otherwise, condensation and dripping may occur.