Справочник Пользователя для Mitsubishi Electronics PLFY-P15

Скачать
Страница из 36
16
Control modes
Control details
3-1. Drain pump control
     •Always drain pump ON during the COOL and DRY mode operation.
   (Regardless of the thermo ON/OFF)
     •When the operation mode has changed from the COOL or DRY to the others  
   (including Stop), OFF the control after the drain pump ON for 3 minutes.
Float switch control
 
• Float switch control judges whether the sensor is in the air or in the water by 
 
  turning the float switch ON/OFF.
 
  In the water: Detected that the float switch is ON for 15 seconds.
 
  In the air     : Detected that the float switch is OFF for 15 seconds.
(1) Initial setting: Start at COOL mode and horizontal vane.
(2) Vane  position: 
Horizontal →Downward A →Downward B →Downward C→Downward D→Swing→Auto
(3) Restriction of the downward vane setting 
When setting the downward vane A, B, C or D in [Med1], [Med2] or [Low] of the 
fan speed notch, the vane changes to horizontal position after 1 hour have passed.
4. Vane 
(up/down vane change)
3. Drain pump 
Remarks
· "ONLY 1 Hr"  
  appears on the 
  wired remote
  controller.
ON
OFF
15sec.
15sec.
15sec. 1min.30sec.
1min.30sec.
From the preceding page.
Float SW
In the water
In the air
In the water
Error
postponement
Drain pump
abnormal