24
Output
(Phase)
Output
{
1
1
ON
{
2
ON
{
3
OFF
{
4
OFF
2
OFF
ON
ON
OFF
3
OFF
OFF
ON
ON
4
ON
OFF
OFF
ON
<Output pulse signal and the valve operation>
2 Linear expansion valve operation
3 Trouble shooting
D
A
E
B
C
Open
Open
Extra tightening (200~800 pulse)
Pulse number
Outdoor unit R410A model   : 1400 pulse
Outdoor unit R22 model       : 2000 pulse
Opening a valve
all the way
Close
Close
V
alve position (capacity)
Closing a valve : 1 → 2 → 3 → 4 → 1
Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.
Note:
• When linear expansion valve operation stops, all output phase 
become OFF.
• At phase interruption or when phase does not shift in order, motor 
does not rotate smoothly and motor will lock and vibrate.
• When the switch is turned on, 2200 pulse closing valve signal will 
be sent till it goes to point 
A
 in order to define the valve position.
• When the valve moves smoothly, there is no sound or vibration 
occurring from the linear expansion valves, however, when the 
pulse number moves from 
E
 to 
A
 or when the valve is locked, 
more sound can be heard than in a normal situation.
• Sound can be detected by placing the ear against the screw driver 
handle while putting the screw driver tip to the linear expansion 
valve.
6
5
4
3
2
1
LED
1k
Symptom
Check points
Operation circuit 
failure of the micro 
processor
Disconnect the connector on the controller board, then con-
nect LED for checking.
When power is turned on, pulse signals will output for 10 
seconds. There must be some defects in the operation circuit 
if the LED does not light while the signals are output or keeps 
lighting even after the signals stop.
Countermeasures
Exchange the indoor con-
troller board at drive circuit 
failure.
Linear expansion 
valve mechanism is 
locked.
Valve does not close 
completely.
Wrong connection 
of the connector or 
contact failure
To check the linear expansion valve, operate the indoor unit 
in fan mode and at the same time operate other indoor units 
in cooling mode, then check the pipe temperature  <liquid 
pipe temperature> of the indoor unit by the 
outdoor multi controller board operation 
monitor.  During fan operation, linear expan-
sion valve is closed completely and if there 
is any leaking, detecting temperature of 
the thermistor will go lower.  If the detected 
temperature is much lower than the tem-
perature indicated in the remote controller, 
it means the valve is not closed all the way.  
It is not necessary to exchange the linear expansion valve, if 
the leakage is small and not affecting normal operation.
Thermistor
(Liquid pipe)
Linear
expansion
valve
Motor will idle and make a ticking noise when the motor is 
operated while the linear expansion valve is locked. This tick-
ing sound is the sign of the abnormality.
Check the color of lead wire and missing terminal of the con-
nector.
Exchange the linear expan-
sion vale.
Exchange the linear expan-
sion valve.
If large amount of refriger-
ant is leaked, exchange 
the linear expansion valve.
Disconnect the connector 
at the controller board, 
then check the continuity.
Measure the resistance between each coil (white-red, yellow-
brown, orange-red, blue-brown) using a tester. It is normal if 
the resistance is in the range of 150' ±10%.
Short or breakage 
of the motor coil of 
the linear expansion 
valve