Appendix 3. Compliance with European EC Directives 
 
 
 
 
 
A3 - 4
 
(6) Peripheral 
devices 
[1]  Use EN/IEC Standards compliant parts for the circuit breaker and contactor. 
[2]  Select circuit breaker with instantaneous trip function. (Trip within 30 second when over 
current of 600%). Apply Annex C of EN60204-1 for sizing of the circuit breaker. 
 
 
(7) Miscellaneous 
[1]  Refer to the next section "EMC Installation Guidelines" for methods on complying with the 
EMC Directives. 
[2]  Ground the facility according to each country's requirements. 
[3]  The control circuit connector (
) is safely separated from the main circuit ( ). 
[4]  Inspect the appearance before installing the unit. Carry out a performance inspection of the 
final unit, and save the inspection records.  
 
 