Appendix 4. EMC Installation Guidelines 
 
 
 
 
 
A4 - 4
Appendix 4-4-2  Measures for door  
 
[1]  Use metal for all materials configuring the door.  
[2]  Use an EMI gasket or conductive packing for the contact between the door and control panel unit. 
[3]  The EMI gasket or conductive packing must contact at a uniform and correct position of the metal 
surface of the control panel unit. 
[4]  The surface of the control panel unit contacted with the EMI gasket or conductive packing must 
have conductance treatment.  
 Example) 
 
Weld (or screw) a plate that is plated (with nickel, tin). 
 
EMI gasket
 
Packing
 
Carry out conductance treatment on 
sections that the EMI gasket contacts. 
Door
 
Control panel
 
[5]  As a method other than the above, the control panel unit and door can be connected with a plain 
braided wire. In this case, the panel and door should be contacted at as many points as possible. 
 
Appendix 4-4-3  Measures for operation board panel 
 
[1]  Always connect the operation board and indicator with an earthing wire. 
[2]  If the operation board panel has a door, use an EMI gasket or conductive packing between the door 
and panel to provide electrical conductance in the same manner as the control panel. 
[3]  Connect the operation board panel and control panel with a sufficiently thick and short earthing 
wire. 
 
 
Appendix 4-4-4  Shielding of the power supply input section 
 
[1]  Separate the input power supply section from other parts in the control panel so that the input 
power supply cable will not be contaminated by radiated noise. 
[2]  Do not lead the power line through the panel without passing it through a filter. 
 
Drive unit 
Power  
line filter
 
Breaker 
Control panel 
AC input
Radiated 
noise 
Shielding 
plate 
Control panel 
Power  
line filter
 
Breaker 
AC input
Radiated 
noise 
Drive unit 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The power supply line noise is eliminated 
by the filter, but cable contains noise again 
because of the noise radiated in the control 
panel.
 
 
Use a metal plate, etc., for the shielding 
partition. Make sure not to create a 
clearance.