Appendix 4. EMC Installation Guidelines 
 
 
 
 
 
A4 - 8
Appendix 4-6  EMC countermeasure parts 
 
Appendix 4-6-1  Shield clamp fitting 
 
The effect can be enhanced by connecting the cable directly to the earthing plate. 
Install an earthing plate near each panel's outlet (within 10cm), and press the cable against the earthing 
plate with the clamp fitting. 
If the cables are thin, several can be bundled and clamped together. 
Securely earth the earthing plate with the frame ground. Install directly on the cabinet or connect with an 
earthing wire. 
Contact Mitsubishi if the earthing plate and clamp fitting set (AERSBAN-
 SET) is required. 
 
 
View of clamp section
 Outline drawing 
Peel the cable sheath at the clamp section.
Cable 
Cable 
Earthing plate
Earthing plate 
Clamp fitting
(Fitting A, B)
Clamp fitting 
2-Ø5 hole 
Installation hole 
[Unit: mm] 
Note 1 
M4 screw
Shield sheath 
 
(Note 1)  Screw hole for wiring to earthing plate in cabinet. 
(
 
Note 2)  The earthing plate thickness is 1.6mm. 
 
A B  C  Enclosed 
fittings 
 
AERSBAN-DSET 
100 
86 
30 
Clamp fitting A 
 2 
Clamp fitting A 
70 
AERSBAN-ESET 
70 
56 
Clamp fitting B 
 1 
Clamp fitting B 
45 
 
 
CAUTION
 
Shield of spindle detector cable is not connected to FG (earth). Do not earth the 
cable shield with cable clamp, etc.