Справочник Пользователя для Mitsubishi Electronics E70

Скачать
Страница из 214
E70 Series Connection Manual
4.3 Connection of Operation Panel I/O Unit
93
4.3.3 Connecting with Manual Pulse Generator (MPG)
Both 5V power supply type (UFO-01-2Z9) and 12V power supply type (HD60C) manual pulse generator can be used. 
Take the maximum cable length, etc. into consideration when selecting. 
(Note)
Set one of the following parameters which is suitable for your manual pulse generator.
- 5V manual pulse generator (UFO-01-2Z9) : #1240 set12/bit0 = 1 (100 pulse/rev)
-12V manual pulse generator (HD60C)         : #1240 set12/bit0 = 0 (  25 pulse/rev)
(1) Connecting with 5V manual pulse generator (maximum cable length: 20m)
Connect the 5V manual pulse generator to the connector MPG.
(2) Connecting with 12V manual pulse generator (maximum cable length: 50m)
Connect the 12V manual pulse generator to the connector MPG.
(Note 1) When selecting a manual pulse generator, make sure that its case and 0V terminal are insulated. 
(Note 2) Select 25pulse/rev or 100pulse/rev on the parameter screen. 
<Related items>
Cable drawing: “Cable: F023/F024 Cable"
Connector pin assignment: "General Specifications: Operation Panel I/O Unit" (MPG connector)
  5V 0V    A    B
NO.1
NO.2
NO.1
  5V 0V    A    B
  5V 0V    A    B
MPG
 
F023 cable
5V manual pulse 
generator
(Rear view)
F024 cable
When connecting one 5V 
manual pulse generator
When connecting two 5V 
manual pulse generators
Operation panel 
I/O unit
12V 0V    A    B
NO.1
NO.2
NO.1
12V 0V    A    B
12V 0V    A    B
MPG
 
F320 cable
12V manual pulse 
generator 
HD60C  (Rear view)
F321 cable
When connecting one 
12V manual pulse 
generator
When connecting two 
12V manual pulse 
generators
Operation panel 
I/O unit