AACC 2000 Carbon                                                                       Nov.  1, 1997
44
 Alarms
 
Alarm annunciation
 
Alarms are flashed as messages in the Home display.   A new alarm is displayed as a
double flash followed by a pause, old (acknowledged) alarms as a single flash followed
by a pause.  If there is more than one alarm condition, the display cycles through all the
relevant alarm messages.  Table 2-1 and Table 2-2 list all of the possible alarm messages
and their meanings.
 
Alarm acknowledgement and resetting
 
Pressing both 
 and 
 at the same time will acknowledge any new alarms and reset
any latched alarms.
 
Alarm modes
 
Alarms will have been set up to operate in one of several modes, either:
 Non-latching, which means that the alarm will reset automatically when the Process
Value is no longer in the alarm condition.
 Latching, which means that the alarm message will continue to flash even if the
alarm condition no longer exists and will only clear when reset.
 Blocking, which means that the alarm will only become active after it has first
entered a safe state on power-up.
 
Alarm types
 
There are two types of alarm: Process alarms and Diagnostic alarms.
 
Process alarms
 
These warn that there is a problem with the process which the controller is trying to
control.
 
 
Alarm
Display
 
What it means
 
_
FSL*
 
PV Full Scale Low alarm
 
_
FSH*
 
PV Full Scale High alarm
 
_
dEv*
 
PV Deviation Band alarm
 
_
dHi*
 
PV Deviation High alarm
 
_
dLo*
 
PV Deviation Low alarm
 
_
LCr*
 
Load Current Low alarm
 
p.FLt
 
Probe impedance test
 
fault.
 
 
* In place of the dash, the first character will indicate the alarm number.
 
Table 2-1  Process alarms
 
Alarm
Display
 
What it means
 
_
FL2*
 
Input 2 Full Scale Low
alarm
 
_
FH2*
 
Input 2 Full Scale High
alarm
 
_
LOP*
 
Working Output Low
alarm
 
_
HOP*
 
Working Output High
alarm
 
_
LSP*
 
Working Setpoint Low
alarm