Справочник Пользователя для Sun Microsystems SL8500

Скачать
Страница из 200
Library Specifications
96154 • Revision K
Chapter 1 Introduction 25
Library Specifications
TABLE 1-8 
Library Specifications 
Physical 
• Hmeight 
• Width 
• Depth (Base Library) 
With 1 expansion module 
With 2 expansion modules 
With 3 expansion modules 
2.37 m (236.6 cm) or 7.76 ft (93.15 in.)
1.7 m (170.8 cm) or 5.6 ft (67.25 in.) 
2.8 m (276.9 cm) or 9.1 ft (109 in.) 
3.7 m (372.1 cm) or 12.2 ft (146.5 in.) 
4.7 m (467.4 cm) or 15.3 ft (184 in.) 
5.6 m (562.6 cm) or 18.5 ft (221.5 in.) 
• Weights 
Base Library 
With 1 expansion module 
With 2 expansion modules 
With 3 expansion modules 
• Weight distribution per pad 
Library only: 
1954 kg (4,309 lb) 
2392 kg (5,274 lb) 
2830 kg (6,239 lb) 
3396 kg (7,487 lb) 
454 kg (1,000 lb) 
• Pass-thru  Port 
Height
Width
Depth
Weight
231 cm (91 in.)
17.2 cm (6.76 in.)
150.8 cm (59.4 in.)
121 kg (266 lb) including the mechanisms
• Service Clearances
Customer Interface Module
Drive & Electronics Module
Pass-thru port (between) 
 
66 cm (26 in.) 
85 cm (33.5 in.) 
15.24 cm (6 in.) 
• Temperature
Operating 
Shipping 
Storing 
+16 to +32°C (+60 to +90°F) 
-30.5 to +49°C (-23 to +120°F) 
+4.4 to +32°C (+40 to +90°F) 
+25.6°C (+78°F) maximum, non-condensing
• Wet bulb (operating) 
Humidity
Operating 
Shipping 
Storing 
20% to 80%
5% to 90% 
20% to 80% 
• Operating Heat Output 
44,380 Btu/hr (maximum loading**) 
Calculation for this is: 3.41214 x Watts = Btu/hr 
• Power Consumption 
Single phase configuration and three phase 
configurations 
13.0 kW (maximum loading**) 
13.7 kVA 
kVA = kWatts ÷ Power factor 
The power factor for the SL8500 = 0.95 
**Maximum loading includes 64 tape drives, 4 fully loaded racks, 8 HandBots, all the front frame components 
(CAPs, service door, and elevators), plus redundant control modules.