FS-8700-83 Gamewell 
 
 
 
 
 
 
 
 
Page 7 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com 
 
Length 
Length of Map Descriptor 
 
Controls how many elements of the data 
array are controlled by the map 
descriptor. 
1 – 1000 
Address 
This commonly used parameter has no 
meaning for this driver. If specified it is 
best set to zero. 
Ckt 
Specify the circuit number whose 
message will get stored using this map 
descriptor. 
 
Use the keyword ‘Panel’ if the you wish 
to store data from a panel. All messages 
which do not contain the keyword ‘Ckt’ in 
the action field are deemed to be panel 
messages. 
 
Valid panel numbers are 1-131 
Panel , 1 ,2 , 3 …. 131 
Dev 
The starting device number for the map 
descriptor. The length determines how 
many devices can have their data stored 
using this map descriptor.  
 
Valid circuit numbers are 1-126 but this 
driver allows a device number of zero to 
allow for the storage of messages which 
don’t specify a device number. 
 
Ty 
0 , 1 , 2 … 126 
Clear_On_Reset  
Yes, 
No 
Store_As* 
Only relevant when the 
Data_Type=’Dump’ 
 
This tells the driver to store ignored 
messages in ASCII format or to dump 
them  in ASCII format in the error log. 
AsciiLog 
ASCII 
Value 
Gamewell_Func* 
Only relevant when the function is write.  
 
This parameter tell the driver what type 
of command to send to the panel. 
 
You should always Ack before you 
silence the panel. 
Reset 
Ack 
Silence 
 
Timing Parameters 
 
Column Title 
Function 
Legal Values 
Scan_Interval 
Rate at which data is polled 
>0.1s