USER’S GUIDE
Switched Rack PDU
167
21000
, you would use the following command for a Windows FTP 
client transferring a file to a Rack PDU with an IP address of 
150.250.6.10.
ftp> 
open 150.250.6.10 21000
 
4. Log on using the Administrator user name and password. (
apc
 is the 
default for both.) 
5. Upgrade the AOS. For example:
ftp> 
bin
ftp> 
put apc_hw02_aos_264.bin
 
6. When FTP confirms the transfer, type 
Quit
 to close the session.
7. Wait 20 seconds, and then repeat step 2 through step 6, but in step 5, use 
the application module file name instead of the AOS module.
Instructions for using SCP. 
To use Secure CoPy (SCP) to upgrade the 
firmware for one Rack PDU:
1. Identify and locate the firmware modules described in the preceding 
instructions for FTP.
2. Use an SCP command line to transfer the AOS firmware module to the 
Rack PDU. The following example assumes a Rack PDU IP address of 
158.205.6.185, and an AOS module of 
apc_hw02_aos_264.bin
.)
scp apc_hw02_aos_264.bin apc@158.205.6.185:apc_hw02_aos_264.bin
3. Use a similar SCP command line, with the name of the application 
module instead of the AOS module, to transfer the application module 
to the Rack PDU.
How to upgrade multiple Rack PDUs
Export configuration settings. 
You can create batch files and use an 
APC utility to retrieve configuration settings from multiple Rack PDUs and 
export them to other Rack PDUs.