Справочник Пользователя для Sun Microsystems A3500

Скачать
Страница из 44
Chapter 2
StorEdge A3500 Configurations
2-25
2.5.2
Power Connections
2.5.2.1
Power Sequencer Interconnections
The front and rear power sequencers in the 2x7 cabinet and the 1x8 cabinet must be
interconnected. Make sure an interconnect cable (part number 530-2235-xx) is
connected between the OUT on the front sequencer in 2x7 cabinet and the IN on the
front sequencer in 1x8 cabinet (
). Make sure that the rear sequencers are
likewise connected.
FIGURE 2-22
Connecting the Power Sequencers
2.5.3
Connecting to AC Power Source
Each of the AC power cords connected to the expansion cabinets should be on
independent circuit breakers.
To ensure proper redundancy, if independent circuit breaker boxes or AC power
sources are used, power cords from the same expansion cabinet should be connected
to different circuit breaker boxes or AC power sources.
Caution –
You must ensure that the second rack will not lose power without the
first. Data loss is likely to occur if this happens. DO NOT configure the 3x15
expansion cabinets as shown in
and
. Consult with an
electrician if you do not understand the schematics in the figures.