DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-145
ASAI-PT 
10
Receive FIFO Error Counter Test (#625)
This test reads and clears the BRI port’s Receive FIFO error counter maintained 
on the TN800 circuit pack. This counter is incremented by the circuit pack when 
it detects an overflow of its receive buffers. The test passes if the value of the 
counter is 0 (that is, the error is cleared). If the counter is not zero, the test fails, 
and the value of the counter is displayed in the Error Code field.
This error can occur if signaling frames are being received from a Packet Bus at 
a rate sufficient to overflow the receive buffers on the circuit pack for a port or if 
hardware fault is causing the receive buffers not to be emptied properly. This test 
is useful for verifying the repair of the problem.
.
Clear Error Counters Test (#270)
There are various error counters associated with each ASAI-PT. This test clears 
those counters and triggers the auditing of Layer 3 reinitialization. This test is 
used only to send messages to the ASAI-PT and, therefore, should neither abort 
nor fail. ASAI uses a fixed TEI value of 1.
Table 10-50.
TEST #625 Receive FIFO Error Counter Test 
Error 
Code
Test 
Result
Description/Recommendation
2000
ABORT
Response was not received from the circuit pack within the allowable time 
period.
1. If the test aborts repeatedly a maximum of 5 times, reset the circuit 
pack via the 
busyout board PCSS
 and 
reset board PCSS
 commands.
2. If the test aborts again, replace the circuit pack.
2012
ABORT
Internal system error
2100
ABORT
Could not allocate necessary system resources to run test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
Any
FAIL
The TN800 circuit pack is still detecting errors of this type. The Error Code 
field contains the value of this counter.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to fail, review the results of other tests in the Long 
Test Sequence. Note the results of the Level 1 Status Inquiry test. 
Follow repair procedures for any of the tests that fail. Otherwise, go to 
the next step.
3. If the tests for the endpoints or adjunct pass and the Layer 1 
Transmission Error Counter Test continues to fail, check the wiring to 
the endpoints or adjunct.
PASS
The Layer 1 Transmission error counter was read correctly and has a value 
of 0.