DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-276
CARR-POW (Carrier Port Power Unit) for AC-Powered Systems 
10
Power Unit Query Test (#127)
This test queries the Maintenance/Tape Processor in a Standard system PPN, the 
Duplication Interface circuit pack in a PPN for a system with High or Critical 
Reliability, or the EPN Maintenance circuit pack in an EPN multicarrier cabinet 
system for the status of pair of power units in the specified carrier. If both power 
units are on and functioning, then the test passes. If both are not on and 
functioning, it fails.
PASS
Both power units in the recycled carrier were 
found to be healthy by the Maintenance/Tape 
Processor in a Standard system PPN, the 
Duplication Interface circuit pack in a PPN for a 
system with High or Critical Reliability, or the EPN 
Maintenance circuit pack in an EPN multicarrier 
cabinet system after the power units were 
powered down and back up. If the status LEDs on 
both power units are not showing green, then the 
PR-MAINT (Maintenance/Tape Processor), 
DUPINT (Duplication Interface) circuit pack, or the 
EPN MAINT (Maintenance) circuit pack may have 
incorrectly reported the state of the power units. 
Look for and resolve any alarms on these MOs.
Table 10-83.
TEST #127 Power Unit Query Test 
Error 
Code
Test 
Result
Description/ Recommendation
1000
ABORT
System resources required to run this test are not 
available.
1. Retry the command at one minute intervals a 
maximum of five times.
2. If the test continues to abort, escalate the problem.
Continued on next page
Table 10-82.
TEST #126 Power Unit Recycle Test  — 
Continued
Error Code
Test 
Result
Description/ Recommendation
Continued on next page