DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-708
EXT-DEV ADMIN? N (External Device Alarm) 
10
EXT-DEV ADMIN? N (External Device 
Alarm)
NOTE:
Use this Maintenance Object when the 
External Device Alarm Admin?
 field 
on the 
change system-parameters customer-options
 form is set to (
n
).
In the Standard Reliability PPN the Maintenance Processor (TN786B or TN790) in 
carrier (A) monitors the EXT-DEV alarm leads. In the High or Critical PPN, the 
Duplication Interface (TN772) circuit pack in carrier (A) monitors the EXT-DEV 
alarm leads, and provides status to the Maintenance processor (TN786B or 
TN790) in the active SPE. In the EPN the Maintenance Board (TN775) monitors 
the EXT-DEV alarm leads. The system only recognizes pairs connected to the 1M 
and 1m (ALARM MONITOR) leads. Pairs connected to the 2M, 2m, 3M, 3m, and 
3w are not recognized by the system. Refer to the 
DEFINITY Communications 
System Generic 1 and Generic 3i Wiring,
 555-204-111, for more details.
1.
where UU is an appropriate cabinet number determined via the PORT field from the 
Alarm or Error Log.
MO Name As 
It Appears in 
Alarm Log
Alarm 
Level
Initial System 
Technician 
Command to Run
1
Full Name of MO
EXT-DEV
MAJOR
test environment UU 
External Device Alarm
EXT-DEV
MINOR
test environment UU 
External Device Alarm