DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-785
ISDN-PLK (ISDN-PRI Signaling Link Port) 
10
Signaling Link Board Check (#643)
This test checks the state of the UDS1 Interface circuit pack (TN464C or later) 
transporting the ISDN-PRI Signaling Link.
Signaling Port Packet Bus Loopback Test (#939)
This test verifies the connectivity of an ISDN-PRI Signaling Port (D-channel) 
across the Packet Bus, also known as the LAN bus. It will execute only if the port 
is busied out. Failure of this test indicates a fault associated with the port 
hardware on the circuit pack.
1.
D = Destructive; ND = Nondestructive
Table 10-220.
TEST #643 Signaling Link Board Check 
Error 
Code
Test 
Result
Description/ Recommendation
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1700
ABORT
Rollabout video abort. The PRI terminal adapter associated with this 
D-channel port is detached from the circuit pack. This is a normal 
abort when the rollabout video feature is enabled. To complete test 
on this port, either:
1. Re-attach the disconnected PRI terminal adapter and retry test 
command, or
2. Disable the rollabout video feature on this circuit pack by 
entering 
change ds1 PCCSS
 and set the field 
"Alarm when 
PRI Endpoint Detached?"
 to 
"y."
8
FAIL
The UDS1 circuit pack (TN464C or later) is not in-service.
1. Check the Hardware Error Log for entries logged against 
UDS1-BD and consult the UDS1-BD (UDS1 Interface Circuit 
Pack) Maintenance documentation for repair procedures.
PASS
The UDS1 Interface circuit pack transporting the ISDN-PRI 
Signaling Link Port is in-service.
Continued on next page