DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1135
POWER (Battery & Battery Charger for DC-Powered Systems 
10
Note:
a. This error occurs only in a multi-carrier cabinet and can be ignored but not 
cleared for DC-powered systems.
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when 
inspecting errors in the system. By clearing error codes associated with the 
Battery & Battery Charger Query Test,
 for example, you may also clear errors 
generated from other tests in the testing sequence.
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate 
test description and follow the recommended procedures.
1.
D = Destructive; ND = Nondestructive
769
Any
Battery & Battery Charger 
Query Test (#5) (Error Code 2)
MINOR
ON
test environment P sh r 1
3840 
(a)
1005 
or 
1028
Assoc. Test Battery & Battery 
Charger Query Test (#5)
ON
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
Battery & Battery Charger Query
 Test (#5)
X
X
ND
AC Power Query Test (#78) (a)
X
X
ND
Emergency Transfer Query Test (#124) (c)
X
X
ND
Cabinet Sensors Query Test (#122) (d)
X
X
ND
External Alarm Lead Query Test (#120) (e)
X
X
ND
Analog Ring Generator Initialization Test (#117) (f)
X
X
ND
Analog Ring Generator Query Test (#118) (f)
X
X
ND
Table 10-333.
Power Error Log Entries  — 
Continued
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off
 Board
Test to Clear Value
Continued on next page