DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1200
RING-GEN (Analog Ring Generator) 
10
Hardware Error Log Entries and Test to Clear 
Values
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the following tables when 
inspecting errors in the system. By clearing error codes associated with the 
Analog Ring Generator Initialization Test
, for example, you may also clear errors 
generated from other tests in the testing sequence.
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate 
test description and follow the recommended procedures.
1.
D = Destructive; ND = Nondestructive
Analog Ring Generator Error Log Entries
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
0
1
0
Any
Any
Any
test environment UU
1
Analog Ring Generator Query 
Test (#118)
MAJOR
ON
test environment UU r 3
Multicarrier Cabinet
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
Analog Ring Generator Initialization Test (#117)
X
X
ND
Analog Ring Generator Query Test (#118)
X
X
ND
Battery & Battery Charger Query Test (#5) (a)
X
X
ND
AC Power Query Test (#78) (b)
X
X
ND
Power Unit Query Test (Carrier E) (#127) (c)
X
X
ND
Power Unit Query Test (Carrier D) (#127) (c)
X
X
ND
Power Unit Query Test (Carrier A) (#127) (c)
X
X
ND
Power Unit Query Test (Carrier B) (#127) (c)
X
X
ND
Power Unit Query Test (Carrier C) (#127) (c)
X
X
ND
Emergency Transfer Query Test (#124) (d)
X
X
ND
Cabinet Sensors Query Test (#122) (e)
X
X
ND
External Alarm Lead Query Test (#120) (f)
X
X
ND