Maintenance Object Repair Procedures 
Page 10-1227
SHDW-CIR (Common Shadow Circuit) 
10
SHDW-CIR (Common Shadow 
Circuit)
The Common Shadow Circuit is that portion of the Duplication Interface circuit 
pack that is responsible for memory shadowing in a High or Critical Reliability 
system. All memory writes on the active SPE are detected by the Common 
Shadow Circuit on the active Duplication Interface circuit pack via the Memory 
Bus (M-BUS—bus used by control complex circuit packs to write/read memory 
and to communicate with one another). The write information is then passed to 
the Common Shadow Circuit on the Standby Duplication Interface circuit pack 
via the ICC which then executes the write into the Standby Memory circuit pack 
via the Standby M-BUS. In this way, the Standby SPE is kept up-to-date with the 
Active SPE and, as a result, is always ready to take over for the Active SPE.
Refer to DUPINT (Duplication Interface Circuit Pack) Maintenance 
documentation for a detailed description of SPE-to-SPE connectivity and 
STBY-SPE (Standby SPE) Maintenance documentation for a description of how 
the Standby SPE is maintained.
1.
Determine the carrier to test via the Port field from the Alarm or Error Log.
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to 
Run
Full Name of MO
SHDW-CIR
1
MAJOR
test duplication 1C sh
Common Shadow Circuit