DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1321
SW-CTL (Switch Control) 
10
Switch Control EPN Maintenance Board Interface 
Test (#324)
Loop back messages are sent to the Switch Control via the interface used for 
EPN maintenance circuit pack messages. The messages are returned to the SPE 
for verification via the same interface.
Table 10-400.
TEST #324 Switch Control EPN Maintenance Board Interface Test 
Error 
Code
Test 
Result
Description/ Recommendation
1005
ABORT
The system does not contain an EPN, so this test is not executed.
1030
ABORT
The component on which the test was to be run is on the Standby SPE. This 
test may only be run on this component when it resides on the Active SPE.
1. For recommended maintenance procedure, refer to ABORT Error 
Code 1030 in STBY-SPE Maintenance documentation.
32400
ABORT
Test disabled via software patch.
2012 
32413 
32416 
32423 
32425
ABORT
Internal system error
2013 
32411 
32421
ABORT
Could not allocate the necessary system resources to run test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
32414 
32417 
32424 
32427
ABORT
The messages failed to return (timed out) and were not verified.
1. Retry the command at 1-minute intervals a maximum of five retries.
2. If the test continues to abort and SW-CTL Test #325 passes, there is 
not a problem, but if SW-CTL Test #325 fails, follow the 
recommendations for SW-CTL Test #325.
1029 
2014 
2015 
2016 
2017 
2018 
2020 
2022 
2024 
2025 
2051
ABORT
Refer to “Standby SPE” for a description of these error codes.
ABORT
Refer to “STBY-SPE” for a description of these error codes.
Continued on next page