DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1338
SYS-PRNT (System Printer) 
10
Network Control circuit pack. If System Printer Link Maintenance cannot restore 
the System Printer Link, the maintenance tests of these individual components of 
the System Printer Link must be executed to diagnose faults.
Procedures for Restoring the System Printer Link
The following procedures should be followed to restore the System Printer Link:
1. Determine the status of the System Printer Link via the 
status sp-link
 
command. Verify that the System Printer Link is not busied out for 
maintenance. On the System Printer Link Status Form, this is indicated by 
a "no" in the "Maintenance Busy?" field. If the System Printer Link has been 
busied out, issue the 
release sp-link
 command. If the link is "down," 
proceed to Step 2.
2. Issue the 
display system feature
 command to determine the destination 
of the System Printer Link.
If the destination is an 
extension number
, enter the 
status data-module 
<extension>
 command and verify that the data extension is 
in-service/idle. If the data extension is NOT available, refer to the 
"Port/Channel Number" field on the "Data-Module Status" Form. Look for 
errors and/or alarms on the circuit pack with which this extension is 
associated. Refer to the appropriate MO documentation for recommended 
repair strategy. Continue with Step 3.
If the destination is 
eia
, look for PR-MAINT errors in the Hardware Error 
Log. If errors are present, refer to Maintenance/Tape Processor 
Maintenance documentation, and continue with Step 5.
3. Determine if a data channel on the Network Control circuit pack is 
in-service/idle as follows:
a. Use the 
list data-module
 command to find out the extension 
numbers of the data channels on the Network Control circuit pack. 
(There is a maximum of 4. They are listed as "netcon" on the Active 
SPE. Ignore the Standby data channels.)
b. Enter the 
status data-module <extension>
 command to verify that 
at least one Active data channel is in-service/idle.
4. If four data channels are administered and none are available, then look 
for DATA-CHL/DATA-CON/DATA-BD errors in the Hardware Error Log. If 
errors are present, refer to these MO sections for recommended 
maintenance strategy. When problems (if any) with 
DATA-CHL/DATA-CON/DATA-BD have been resolved, continue with Step 
5.
If fewer than four data channels are administered, then use the 
add 
data-module
 command to add a network control data module to the 
system.
5. Verify the availability of the external SYS-PRNT output device as follows: