DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1407
TDM-BUS (TDM Bus) 
10
TDM Bus Clock Parameter Update Test (#151)
This action updates the Tone-Clock internal circuit pack parameters. Tone-Clock 
circuit pack:
Disable in-line duplication status messages.
Disable in-line subrate frame maintenance messages (TN768, TN780 
only).
Set the PPM threshold at 60 PPM for TN768 and TN780. Set the PPM 
threshold at 85 PPM for TN2182.
Enable PPM threshold switching
ANY
 
(cont’d.)
FAIL
4. If there are no other errors besides Error Type 1537 against TDM-CLK 
and if this error was logged against the Tone-Clock circuit pack that 
provided the current system synchronization reference (use the 
status 
synchronization
 command to determine this), replace the defective 
Tone-Clock circuit pack. 
!
WARNING:
Since service may be disrupted when the following procedures are 
carried out, try to perform the following steps when it is convenient for 
the customer.
5. If the Tone-Clock circuit pack under test is in the Active mode but is not 
providing the current system synchronization reference, switch the 
synchronization reference to the Tone-Clock circuit pack under test 
using the 
set synchronization PC
 command. Rerun the test. If the test 
still fails, replace the defective Tone-Clock circuit pack.
6. If the Tone-Clock circuit pack under test is in the Standby mode place 
it in the Active mode via the command 
set tone-clock PC
. Switch the 
synchronization reference to the Tone-Clock circuit pack under test 
using the 
set synchronization PC
 command. Rerun the test. If the test 
still fails, replace the defective Tone-Clock circuit pack.
PASS
The Tone-Clock circuit pack does not detect timing any PPM errors. This 
indicates that the external synchronization timing source is valid or that the 
system synchronization reference is a Tone-Clock circuit pack. The 
status 
synchronization
 command should be used to verify that the desired 
synchronization reference is providing timing for the system.
Table 10-426.
TEST #150 TDM Bus Clock PPM Inquiry Test  — 
Continued
Error 
Code
Test 
Result
Description/ Recommendation