DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Circuit Packs and Power 
Page 2-7
Power 
2
NOTE:
When EPN power is interrupted for greater than the cabinet holdover but 
less than the control carrier holdover, calls in the control carrier are held for 
the duration of the interruption but are dropped when power is restored.
Single-Carrier Cabinets
In single-carrier cabinets, there is no internal AC wiring or distribution and no 
software interaction with the power system. The power supplies themselves take 
about 250 milliseconds for the voltages to drop below limits.
The control cabinet that houses the Switch Processing Element (SPE) is the only 
cabinet that has an internal battery reserve. All other control cabinets and port 
cabinets have the 250 millisecond power supply decay delay, after which all 
connections and links associated with the cabinets are dropped.
1.
The holdover times listed are in effect if the EPN contains a TN775 maintenance circuit pack. 
However, if the EPN contains a TN775B maintenance circuit pack, the holdover time for the entire 
cabinet is 10 seconds, and the holdover time for the control carrier is 10 minutes.
Table 2-3.
Response to Power Service Interruption with an Internal Holdover Battery 
System and 
Configuration
Cabinet
Holdover for 
Entire Cabinet 
(in seconds)
Holdover for 
Entire Control 
Carrier (in minutes)
Standard
PPNMCC
10
10
High, Critical
PPNMCC
10
5
Standard/High, Critical
PPN SCC/ESCC
1/4
2
Standard/High, Critical
1
EPN MCC
15
none
Standard/High, Critical
EPN SCC/ESCC
1/4
none
Table 2-4.
Types of Cabinet Power Interruption
System and 
Cabinet
Shorter Holdover 
Than Entire 
Cabinet
Longer Holdover than 
Entire Cabinet, Shorter 
Holdover than Control 
Carrier
Longer Holdover 
Than Control 
Carrier
PPN SCC
No calls dropped
All calls dropped
System reloads
EPN SCC
No calls dropped
All calls dropped
System reloads