DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-12
AC-POWER 
10
AC Power for DC-Powered Systems
NOTE:
For environment maintenance, the PPN or EPN cabinet configuration 
aspects in a High or Critical Reliability system are irrelevant.
1.
Where P is an appropriate port network number determined via the PORT field from the 
Alarm or Error Log.
1
(cont’d.)
FAIL
(cont’d.)
2. Procedures for a Global MCC (J58890CH):
a. For a nominal holdover system if there is no AC power at the wall 
outlet, then the problem is not with the system itself. Power must be 
restored to the wall outlet.
b. If there is AC power at the wall outlet, then there could be a 
problem with the Rectifiers (RM850), Battery Interface Unit, or 
battery. Resolve all alarms logged against the POWER 
Maintenance Object, and rerun the test. If the test still fails, the BIU 
may be defective. Check to see if the BOD alarm LED is “on”, on 
the BIU. If the BOD LED is “on” replace the Battery Interface Unit 
(BIU). If the BOD LED is “off” and the BOK LED is “on” then the 
SYSAM or the EPN Maintenance circuit pack may be incorrectly 
reporting the problem. Resolve all alarms against these 
Maintenance Objects and rerun the test.
100
FAIL
The switch is currently without AC power, and AC Power maintenance is in 
the middle of timing the NPH interval.
1. Follow the repair steps outlined above for Error Code 1.
PASS
The PR-MAINT (Maintenance/Tape Processor) in a PPN in a system 
without High or Critical Reliability, the DUPINT (Duplication Interface) 
circuit pack in a High or Critical Reliability system PPN, or the EPN MAINT 
(Maintenance) circuit pack in an EPN multicarrier cabinet system has 
reported that the switch has AC power. If there is no AC power at the wall 
outlet, then look for and resolve all alarms against the appropriate MO 
listed.
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to Run
1
Full Name of MO
AC-POWER
WARNING
test environment P
AC Power
Table 10-4.
TEST #78 AC Power Query Test  — 
Continued
Error 
Code
Test 
Result
Description / Recommendation
Continued on next page