4-2 Parameter Index
MN850
Applications Menu
 Continued   
Small Pump
Name
Start Pedestal %
Start Time
Current Limit Level
10
5
3.5
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
10
30
%
S
Current Limit Time
25 S
Screw Compressor
Name
Start Pedestal %
Start Time
Current Limit Level
40
7
7.8125
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
25 S
Large Pump
Name
Start Pedestal %
Start Time
Current Limit Level
10
7
3.5
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
10
45
%
S
Current Limit Time
25 S
Rotary Compressor
Name
Start Pedestal %
Start Time
Current Limit Level
35
7
3.5
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
25 S
Low Inertia Fan
Name
Start Pedestal %
Start Time
Current Limit Level
30
15
3.5
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
30 S
Crusher
Name
Start Pedestal %
Start Time
Current Limit Level
40
3
3.5
%
S
*FLC
Optimise Rate
2.8125
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
60 S
High Inertia Fan
Name
Start Pedestal %
Start Time
Current Limit Level
40
3
2.8125
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
60 S
Grinder
Name
Start Pedestal %
Start Time
Current Limit Level
40
3
2.8125
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
60 S
Conveyor
Name
Start Pedestal %
Start Time
Current Limit Level
10
10
3.5
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
7
%
S
Current Limit Time
30 S
High Torque Start
Name
Start Pedestal %
Start Time
Current Limit Level
60
3
4.375
%
S
*FLC
Optimise Rate
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
12 S
Reciprocating Compressor
Name
Start Pedestal %
Start Time
Current Limit Level
45
3
3.5
%
S
*FLC
Optimise Rate
15
Auto End Start
Soft Stop Smoothing
Auto 3MC
Low Voltage SoftStop
Auto Bypass
Auto Pedestal
Auto Stop
Auto Jog
Auto End Stop
Stop Pedestal %
Stop Time
0
0
%
S
Current Limit Time
25 S