5. Storing the Battery Pack
The Battery Pack should be stored in a covered location and with
its batteries in a fully-charged state (reports 100% capacity to the UPS).
In extended storage, use the UPS to refresh the Battery Pack every six
months in environments where the temperature is –15 to +30 °C
(+5 to +86 °F). Refresh the Battery Pack every three months in environ-
ments where the temperature is +30 to +45 °C (+86 to +113 °F).
6. Battery Life
6.1 Battery life
You can expect to receive three to six years of service from the Battery
Pack’s batteries. When the batteries can no longer sustain a charge, the
Replace Battery indicator on the front panel of the UPS lights. Refer to
Section 4 to replace the batteries.
7. Specifications
7.1 Battery
Battery type:
Two (UXBP24L) or Four (UXBP24,
UXBP48) spill-proof, maintenance-free,
sealed lead-acid
Nominal battery
pack voltage:
24 Vdc (Model UXBP24, UXBP24L)
48 Vdc (Model UXBP48)
Typical battery life:
3 to 6 years, depending on environment and
use
Recharge time:
See table in Section 7.4
7.2 Environment
Operating
temperature:
0 to +40 °C (+32 to +104°F)
Storage
temperature:
–15 to +45 °C (+5 to +113 °F)
Operating and
storage relative
humidity:
0 to 95%, non-condensing
Operating
elevation:
0 to 3,000 m (10,000 ft)
Storage
elevation:
0 to 15,000 m (50,000 ft)
990-0191B     revision 3     2/98
7.3 Physical
UXBP24L
UXBP24/UXBP48
Size (H´W´D):
31.0 x 44.7 x 75.4 cm
(12.2 x 17.6 x 29.7 in.)
31.0 x 44.7 x 75.4 cm
(12.2 x 17.6 x 29.7 in.)
UXBP weight:
(with batteries)
74.5 kg (164.0 lbs)
127.3 kg (280.0 lbs)
Shipping weight:
(with batteries)
90.0 kg (198.0 lbs)
142.7 kg (314.0 lbs)
7.4 Runtime versus load
Run times are typical at 25 °C (77 °F).
Run Time
Runtime with SU1000UXINET
Runtime required
Load 
Ò
1 hr
2 hr
3 hr
4 hr
6 hr
8 hr
500 VA
1 UXBP24L
1 UXBP24
1 UXBP24
+
1 UXBP24L
1000 VA
1 UXBP24L
1 UXBP24
1 UXBP24 +
1 UXBP24L
Runtime with SU2200UXINET/SU3000UXINET
Runtime required
Load 
Ò
1 hr
2 hr
3 hr
4 hr
6 hr
8 hr
500 VA
1 UXBP48
2 UXBP48
1000 VA
1 UXBP48
2 UXBP48
3 UXBP48
1500 VA
1 UXBP48
2 UXBP48
3 UXBP48
4 UXBP48
2000 VA
1 UXBP48
2 UXBP48
3 UXBP48
4 UXBP48
5 UXBP48
3000 VA
1 UXBP48
2 UXBP48
3 UXBP48
4 UXBP48
5 UXBP48
6 UXBP48
Recharge Time
Number of UXBP Battery Packs
1
2
3
4
5
6
1000 VA UPS
15
19
23
27
31
35
2200 VA UPS
3000 VA UPS
8
11
13.5
16
18.5
21
* Recharge to 90% capacity after discharge into 50% of rated full load.