Справочник Пользователя для Mitsubishi Electronics FX2N-5A

Скачать
Страница из 108
Example program 9
9-1
9.
Example program
9.1
Program example for analog input/output
The section introduces an example program to manipulate analog input/output using the 
FX
2N
-5A.
Condition
System configuration: 
The FX
2N
-5A (unit No. 0) is connected as a special function block nearest to the FX
0N
/
FX
1N
/FX
2N
/FX
2NC
 Series PLC main unit.
Input mode: 
CH1 and CH2 : Mode 0 (voltage input, -10 to +10 V 
→ -32000 to +32000)
CH3 and CH4 : Mode 1 (current input, +4 to +20 mA 
→ 0 to 32000)
Output mode: 
Analog output channel: Mode 0 (voltage output, -32000 to +32000 
→ -10 to +10 V)
Number of times of averaging: 
10 in each input channel
I/O characteristics: 
Standard I/O characteristics (initial value) in each channel
Convenient function: 
Not used.
I/O assignment: 
X000
: Change of analog output value.
X001
: Clears the scale over error.
Y000 to Y007 : Output scale over status of each channel.
Y010 to Y027 : Output of error status.
FX2N-5A Special function block