FX2N-5A Special function block
Buffer Memory (BFM) 7
7-47
7.2.35
BFM 200 to BFM 249 Scaling function (READ/WRITE)
The Scaling function enables an analog input or output curve, for processes that are not linear
over the whole data range. The user can specify up to 5 analog/digital values, that will define
an input characteristic curve.
If the Scaling function is used, the offset/gain settings will become meaningless for this
channel, as the input/output will be calculated by the Scaling function given by the user.
Analog scale value and digital value outside the range selected by BFM 0 and 1 is set.
Offset/gain set value becomes error (BFM 29 b1).
The order of allocating an analog value and a digital value differs for in the input channels and
the output channel.
Table 7.13: Allocation of BFM #200 to #249
Channel No.
Set value kind
BFM No.
Change 
point 1
Change 
point 2
Change 
point 3
Change 
point 4
Change 
point 5
Analog input channel
CH1
Analog scale value
#200
#202
#204
#206
#208
Digital value
#201
#203
#205
#207
#209
Analog input channel
CH2
Analog scale value
#210
#212
#214
#216
#218
Digital value
#211
#213
#215
#217
#219
Analog input channel
CH3
Analog scale value
#220
#222
#224
#226
#228
Digital value
#221
#223
#225
#227
#229
Analog input channel
CH4
Analog scale value
#230
#232
#234
#236
#238
Digital value
#231
#233
#235
#237
#239
Analog output channel
Digital value
#240
#242
#244
#246
#248
Analog scale value
#241
#243
#245
#247
#249