ANCB LEDs Description and Operations, 
Continued 
 
Figure 4-2 shows the edge visible LEDs on the ANCB. The LED labels 
are silk-screened adjacent to each LED on the ANCB. 
Figure 4-2: ANCB/DN LED 
Indicators 
 
CL
 
Use the following Table 4-1 to determine the error condition. FAULT 
errors can only be cleared with a board reset. 
Table 4-1: Error Codes  
NUMBER 
of Blinks 
 
Type of Error 
 
Corrective Action 
RAM FAILURE 
Replace Board 
FLASH FAILURE 
Reload Firmware or 
Replace Board 
ETHERNET FAILURE 
Replace Board 
DataNET FAILURE 
Replace Board 
DUPLICATE IP 
Change Board IP address 
WRONG LOOP 
Change Loop Number 
WRONG JUMPER 
CONFIGURATION 
Check J10 and J11 
Connections 
10 
DUPLICATE UNIT NUMBER 
Change Unit Number 
50  
  Troubleshooting 