Справочник Пользователя для Varec 8315 Series
Appendix
TankGate Interface
ii
Installation and Operations Manual
1.2.1
Modbus Map
Address
Type
Number
Parameter
Data Type
5000
LJ2000
0
Command
CODED
5001
LJ2000
0
Level
REAL
5003
LJ2000
0
Temp
REAL
5005
LJ2000
0
Value
REAL
5007
LJ2000
0
Status
HEX
5008
LJ2000
0
PntStatus
IHEX
5009
LJ2000
0
Elapse
TIME
There are a total of 50 GPE points. There are a total of 11 registers available per gauge. The addresses are sequential. The addresses range from
5000 to 5550
4000
SCALER
0
Value
REAL
4002
SCALER
0
Value1
INTEGER
4003
SCALER
0
PntStatus
UBYTE
4004
SCALER
0
Elapse
TIME
4006
SCALER
1
Value
REAL
4008
SCALER
1
Value1
INTEGER
4009
SCALER
1
PntStatus
UBYTE
4010
SCALER
1
Elapse
TIME
There are a total of 16 SCLAER points. There are a total of 11 registers available per SCALER point The addresses are sequential. The addresses
range from 4000 to 4095
1000
IREG
0
Value1
UINTEGER
1001
IREG
0
Value2
UINTEGER
1002
IREG
0
Value3
UINTEGER
1003
IREG
0
Value4
UINTEGER
1004
IREG
0
Value5
UINTEGER
1005
IREG
0
Value6
UINTEGER
1006
IREG
0
Value7
UINTEGER
1007
IREG
0
Value8
UINTEGER
1008
IREG
0
Value9
UINTEGER
1009
IREG
0
Value10
UINTEGER
1010
IREG
0
Value11
UINTEGER