Appendix
TankGate Interface
ii 
Installation and Operations Manual
1.2.1
Modbus Map
Address 
Type 
Number 
Parameter      
Data Type 
5000
LJ2000 
0
Command        
 CODED 
5001
LJ2000
0
Level          
 REAL 
5003
LJ2000
0
Temp           
 REAL 
5005
LJ2000
0
Value          
 REAL 
5007
LJ2000
0
Status         
 HEX 
5008
LJ2000
0
PntStatus      
 IHEX 
5009
LJ2000
0
Elapse         
 TIME 
There are a total of 50 GPE points. There are a total of 11 registers available per gauge.  The addresses are sequential.  The addresses range from 
5000 to 5550
4000
SCALER 
0
Value          
 REAL 
4002
SCALER 
0
Value1         
 INTEGER 
4003
SCALER 
0
PntStatus      
 UBYTE 
4004
SCALER 
0
Elapse         
 TIME 
4006
SCALER 
1
Value          
 REAL 
4008
SCALER 
1
Value1         
 INTEGER 
4009
SCALER 
1
PntStatus      
 UBYTE 
4010
SCALER 
1
Elapse         
 TIME 
There are a total of 16 SCLAER points. There are a total of 11 registers available per SCALER point  The addresses are sequential.  The addresses 
range from 4000 to 4095
1000
IREG   
0
Value1         
 UINTEGER 
1001
IREG   
0
Value2         
 UINTEGER 
1002
IREG   
0
Value3         
 UINTEGER 
1003
IREG   
0
Value4         
 UINTEGER 
1004
IREG   
0
Value5         
 UINTEGER 
1005
IREG   
0
Value6         
 UINTEGER 
1006
IREG   
0
Value7         
 UINTEGER 
1007
IREG   
0
Value8         
 UINTEGER 
1008
IREG   
0
Value9         
 UINTEGER 
1009
IREG   
0
Value10        
 UINTEGER 
1010
IREG   
0
Value11        
 UINTEGER