the channel is in an overcurrent state, measure the voltage between 
DO and V
sup
. If the voltage is equal to the voltage of the external 
power supply connected to the module, the channel is in an 
overcurrent state.
Resetting Channels After an Overcurrent Condition
After you have determined and fixed the cause of the overcurrent 
condition, reset the channel by turning it off. Alternatively, you can 
disconnect the external power supply from the module. However, 
doing so disconnects power from all of the module channels. 
Normal operation can resume after you correct the overcurrent 
condition and reset the channel.