NI 9481 Operating Instructions and Specifications
Safety Guidelines for Hazardous Locations
The NI 9481 is suitable for use in Class I, Division 2, Groups A, B, 
C, D, T4 hazardous locations; Class I, Zone 2, AEx nC IIC T4 
hazardous locations; and nonhazardous locations only. Follow 
these guidelines if you are installing the NI 9481 in a potentially 
explosive environment. Not following these guidelines may result 
in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors 
unless power has been switched off or the area is known 
to be nonhazardous.
Caution
Do not remove modules unless power has been 
switched off or the area is known to be nonhazardous.
Caution
Substitution of components may impair 
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the system 
in an enclosure rated to at least IP 54 as defined by 
IEC 60529 and EN 60529.