NI WLS/ENET-9163 Carrier User Guide and Specifications
Environmental
The NI WLS/ENET-9163 carrier is intended for indoor use only. For 
outdoor use, mount the system in a suitably rated enclosure.
Operating temperature
(IEC-60068-2-1 and IEC-60068-2-2) .... 0 to 55 °C
Storage temperature
(IEC-60068-2-1 and IEC-60068-2-2) .... –10 to 70 °C
Ingress protection ................................... IP 30
Operating humidity
(IEC-60068-2-56)................................... 10 to 90% RH, noncondensing
Storage humidity (IEC-60068-2-56) ...... 5 to 90% RH, noncondensing
Maximum altitude .................................. 2,000 m 
Pollution Degree (IEC 60664) ............... 2 
Shock and Vibration
To meet these specifications, you must panel mount the 
NI WLS/ENET-9163 carrier and affix ferrules to the ends of the terminal 
lines.
Operational shock .................................. 30 g peak, half-sine, 11 ms pulse 
(Tested in accordance with 
IEC-60068-2-27. Test profile 
developed in accordance with 
MIL-PRF-28800F.)
Random vibration
Operating ........................................ 5 to 500 Hz, 0.3 g
rms
Nonoperating .................................. 5 to 500 Hz, 2.4 g
rms
 
(Tested in accordance
with IEC-60068-2-64. 
Nonoperating test profile
exceeds the requirements of 
MIL-PRF-28800F, Class 3.)