NI 9476 Operating Instructions and Specifications
4
ni.com
Caution
Substitution of components may impair 
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the system 
in an enclosure rated to at least IP 54 as defined by 
IEC 60529 and EN 60529.
Caution
For Zone 2 applications, install a protection 
device between the external power supply and the V
sup
 
pin. The device must prevent the V
sup
-to-COM voltage 
from exceeding 50 V if there is a transient overvoltage 
condition.
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment 
under DEMKO Certificate No. 03 ATEX 0324020X. Each module 
is marked 
 II 3G and is suitable for use in Zone 2 hazardous 
locations. If you are using the NI 9476 in Gas Group IIC hazardous 
locations or in ambient temperatures of –40 °C
≤ Ta ≤ 70 °C, you 
must use the device in an NI chassis that has been evaluated as 
EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.