NI 9476 Operating Instructions and Specifications
Increasing Current Drive
Each channel has a continuous output current of 250 mA. If you 
want to increase the output current to a device, you can connect
any number of channels together in parallel. For example, if you 
want to drive 1 A of current, connect DO<0..3> in parallel as 
shown in Figure 3. You must turn all parallel channels on and off 
simultaneously so that the current on any single channel cannot 
exceed the 250 mA rating.
Figure 3.  Increasing the Current to a Device Connected to the NI 9476
NI 9476 
250 mA 
250 mA 
250 mA 
250 mA 
DO3 
DO1 
DO0 
DO2 
1 A 
Device 
COM 
 
External
Power
Supply
V
sup