NI 9871 Operating Instructions
4
ni.com
Caution
For Zone 2 applications, install a protection 
device between the RS485/RS422 signal cables and the 
NI 9871 RJ-50 jacks (ports 1– 4). The device must 
prevent the RS485/RS422 signal-to-signal or 
signal-to-COM voltage from exceeding 23 V if there is a 
transient overvoltage condition.
Caution
For Zone 2 applications, install a protection 
device between the external power supply and the 
NI 9871 V
sup
 and COM pins. The device must prevent the 
V
sup
-to-COM voltage from exceeding 39 V if there is a 
transient overvoltage condition.
Special Conditions for Hazardous Locations in Europe
This equipment has been evaluated as Ex nA IIC T4 equipment 
under DEMKO Certificate No. 07 ATEX 0626664X. Each module 
is marked 
 II 3G and is suitable for use in Zone 2 hazardous 
locations. If you are using the NI 9871 in Gas Group IIC hazardous 
locations or in ambient temperatures of –40 
°C ≤
 
Ta 
 
70 
°C, you 
must use the device in an NI chassis or controller that has been 
evaluated as EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4 
equipment.