Справочник Пользователя для National Instruments NI 6509

Скачать
Страница из 23
NI 6509 User Guide and Specifications
16
ni.com
Figure 5.  NI 6509 Signal Connections
Protecting Inductive Loads
When inductive loads are connected to outputs, a large 
counter-electromotive force may occur at switching time because of the 
energy stored in the inductive load. These flyback voltages can damage 
the outputs and/or the power supply.
To limit these flyback voltages at the inductive load, install a flyback diode 
across the inductive load. For best results, mount the flyback diode within 
18 inches of the load. Figure 6 shows an example of using an external 
flyback diode to protect inductive loads.
41
43
45
47
67
69
71
73
50, 100
NI 6509
+5 V
+5 V
LED
Port 7
P7<7..4>
Port 0
P0<3..0>
GND
TTL Signal