Chapter 3
Signal Connections
3-10
www.ni.com
Figure 3-5.  Signal Connections for Solid-State Relays
Writing a 0 (logic low) to an output bit closes the relay, and writing a 1 
(logic high) opens the relay.
To both sink and source current with one channel requires an external 
resistor. You can use the solid-state relays of a 6527 device with external 
resistors to drive voltages at TTL or non-TTL levels, from -60 to 60 VDC 
or 30 VAC (42 V peak). 
For isolated power, total current on all channels exceeding 1 A, or voltages 
other than +5 V, you can provide an external power supply. For driving 
non-isolated +5 V outputs totaling less than 1 A—for example, when using 
the 6527 as a TTL-level output device—you can use the +5 V line from the 
6527 device as your voltage source.
Load
R
S
I
f
+5 V
Supply
+
Isolation
Isolated
Ground
Digital
Logic
390 
Ω
DIG+
6527
DIG–
Load
R
S
I
f
+5 V
Supply
+
Isolation
Isolated
Ground
Digital
Logic
390 
Ω
 
DIG+
6527
DIG–
a. Sinking Current
b. Sourcing Current
35 
Ω
35 
Ω
LH1546
LH1546