cFP-2200/2210/2220
26
ni.com
NO APP Switch
Push the NO APP switch to the ON position to prevent a LabVIEW RT 
startup application from running at startup. If you want to permanently 
disable a LabVIEW RT application from running at startup, you must 
disable it in LabVIEW. To run an application at startup, push the NO APP 
switch to the OFF position, create an application using the LabVIEW 
Application Builder, and configure the application in LabVIEW to launch 
at startup. If you already have an application configured to launch at startup 
and you push the NO APP switch from ON to OFF, the startup application 
is automatically enabled. For more information about automatically 
launching VIs at startup and disabling VIs from launching at startup, refer 
to the Running a Stand-Alone Real-Time Application (RT Module) topic of 
the LabVIEW Help.
CONS OUT Switch
With a serial-port terminal program, you can use the CONS OUT switch
to read the IP address and firmware version of the controller. Use a 
null-modem cable to connect the serial port to a computer. Push the switch 
to the ON position. Make sure that the serial-port terminal program is 
configured to the following settings:
9,600 bits per second
Eight data bits
No parity
One stop bit
No flow control
The serial-port terminal program displays the IP address and firmware 
version of the controller, and alerts you when you connect an unsupported 
USB device to the cFP-2220. Keep this switch in the OFF position during 
normal operation.
USER2 and USER1 Switches
You can define the USER2 and USER1 switches for your application. 
To define the switches in an embedded application, use the RT Read 
Switch VI in a LabVIEW RT embedded VI. You can use the FieldPoint 
ReadVI to read defined switches in embedded or unembedded applications. 
For more information about the RT Read Switch VI and the FieldPoint 
Read VI, refer to the LabVIEW Help.