227
Command/Response Reference
Section 11-3
Results Storage Area Response Codes
11-3-12 UDP CLOSE REQUEST
Requests processing to close a socket.
Command Block
Response Block
Results Storage 
Format
Parameters
UDP Socket Number 
(Command)
The UDP socket number to be closed specified as 2 bytes between 1 and 8. 
Results Storage Area 
(Command)
The area in which the results of the command execution are stored. The first
byte specifies the memory area and data type (variable type). The 2nd to 4th
bytes specify the beginning address of the results storage area. Refer to
page 216 for details about the variable types and addresses that can be spec-
ified.
Response Codes
Response code
Description
0000
Normal
003E
Internal buffer cannot be reserved due to high reception load 
(ENOBUFS).
0042
The send destination IP address is a broadcast address and 
the number of bytes sent exceeds 1,472. (EMSGSIZE)
004C
Incorrect network number.
Incorrect destination IP address (EADDRNOTAVAIL). 
004E
Incorrect destination IP address (ENETUNREACH). 
No network number in IP router table. 
Router incorrectly set.
0051
Router incorrectly specified.
Incorrect destination IP address (EHOSTUNREACH). 
04
27
Command 
code
UDP 
socket 
number
Results storage area
04
27
Command 
code
Response 
code
Response 
code
Response code
Description
0000
Normal
0105
Local IP address setting error
0302
CPU Unit error; execution not possible.
1001
Command too large
1002
Command too small
1100
UDP socket number is out of range. 
1101
The variable type for the results storage area is out of range.
1103
Non-zero bit address specified for the results storage area.