Справочник Пользователя для Omron CJ1W-CLK21-V1

Скачать
Страница из 401
286
Troubleshooting Using Indicators
Section 9-1
Node Cannot Participate 
in Data Link
The following table describes the LNK and M/A indicators when a node can-
not participate in the data links.
Data link participation depends on the Controller Link Unit operating normally
and participating in the Network. Refer to Troubleshooting with RUN, ERC,
ERH and INS Indicators
 earlier in this section and check Unit operation before
using the following table.
Indicators
Probable cause
Probable remedy
LNK
M/A
Lit
---
Data link operating normally.
---
Flashing
---
There is an error in the data 
link tables.
If the ERH indicator is lit, reset 
the data link tables.
When manual setting is used, 
either data link tables have not 
been created for the startup 
node or there is an error in the 
data link tables.
Refer to 5-2-2 Manual Setting 
and set data link tables for the 
startup node.
When automatic setting is 
used, either the data link 
parameters for the startup 
node have not been set or 
there is an error in the data link 
tables.
Refer to 5-2-4 Automatic Set-
ting
 
and set the automatic 
parameters for starting the 
data links.
Automatic setting is used with 
1:N allocations, but the device 
does not support this function.
Use a Controller Link Unit that 
supports automatic data link 
creation with 1:N allocations. 
Refer to Automatic Setting on 
page 129 f
or details.
Not lit
Lit
Manually set data links are 
already operating on the same 
Network.
Stop the manually set data 
links that are operating and 
restart the data links.
Not lit
Not lit
Automatically set data links 
are already operating on the 
same Network.
Stop the automatically set data 
links that are operating and 
restart the data links.
There is an error in the startup 
node PLC.
Refer to the PLC’s operation 
manual and correct the error. If 
the error reoccurs, replace the 
PLC.