 Chapter 18 — Connecting the trunks
553-3021-209
Standard 3.00
April 2000
Connecting trunks without a PFTU
Procedure 39
Connecting trunks without a PFTU
1
From the assignment record, determine the location of the trunk 
connection and its associated Terminal Number (TN) at the 
cross-connect terminal.
2
With cross-connect wire, connect the trunk to the TN.
Make sure that the wiring is not reversed and is on the correct 
terminals.
Tables 57 to 59 list the connections for trunks. For trunk connections 
for Europe, see Tables 60 to 68. For trunk connections for the UK, see 
Tables 69 to 75.
—————————— End of Procedure ——————————
Connecting trunks with a PFTU
Procedure 40
Connecting trunks with a PFTU
1
Locate the PFTU terminal blocks at the cross-connect terminal.
2
Cross-connect the first pair of the assigned PFT to the telephone.
See Table 56 on page 255 for PFTU connections.
3
Cross-connect the second pair of the PFT to the TN assigned to 
the telephone. 
4
Cross-connect the third pair of the PFT to the central office trunk. 
5
Cross-connect the third pair of the PFT to the TN assigned to the 
trunk.
6
Repeat for each trunk assigned to the PFTU.
—————————— End of Procedure ——————————