Справочник Пользователя для Telular TG-9

Скачать
Страница из 6
56037002                                               - 2 -                                   © 2007 Telular Corporation 
 
 
Device Profile Options 
 
The Telguard TG-9 Profile is stored in the Telular Communications Center and defines how each unit 
operates. One profile may be used for multiple units. The profile is uploaded to the Telguard TG-9 
when it is activated, there is no field programming needed. 
 
Trip and Restore Reporting 
The TG-9 is programmed to send trips on all zones (not restorals). The profile can be set so that 
restores are transmitted. Changes will affect all trip zones. 
•  Profile Options: Report Restoral / Do Not Report Restoral 
 
Zone 1: Trip Input or Bell Input 
Zone 1 on the TG-9 can be programmed as a normal trip input (default), or as a Bell Input. Bell 
input is ANSI standard Fire (3 rings, pause) and Burg (steady on).  
•  Profile Options: Trip Input / Bell Input 
Note:  Do not connect E.O.L. resistor if using bell input. 
Note:  If using Bell input, Bell must be connected per Table 1 on page 5 before 
activating. Make sure there are no Bell alarms in progress before activating.  
 
Zone 6: Trip Input or Shunt 
Zone 6 on the TG-9 can be used as a shunt (default) or as a normal trip input. When in shunt 
mode, a switch can be used to enable or disable alarm functions. When the switch is in an “ON or 
SHORTED” state alarm functions will be disabled. 
•  Profile Options: Shunt / Trip Input 
 
 
 Report Shunt Activity / Do Not Report Shunt Activity  
 
Zones 2 - 5: Trip inputs 
Zones 2 - 5 are standard trip inputs. 
 
Swinger Option 
The TG-9 can be programmed for a swinger setting. Should a single zone trip more than X times 
in Y minutes, the system will send no more events for that zone until Z minutes have passed with 
no trips. 
•  Profile Options: Swinger Option On / Off 
 
 
 Number of Events (1 – 99) 
 
 
 During Time Period (1 – 99 Minutes) 
 
              Time to Restore (1 – 99 Minutes) 
 
STC Trip Output
 
The STC trip output is a Normally Closed contact with four modes. 
Mode 1: It acts as a supervisory output, monitoring for No Cellular Service (NSC), Power Failure 
(PFC), Failure to Communicate (RFC),  
Mode 2: It acts as an alarm or bell driver, tripping the alarm system or sounding an alarm bell 
when a zone or zones on the TG-9 are tripped. Output will time out after 15 minutes. 
Mode 3: It acts as an auxiliary output, which will close or open based on incoming signals.  
Mode 4: the output is disabled 
•  Profile Options: Mode 1 / Mode 2 / Mode 3 / Mode 4