Group 11 Fan and Pump Control Parameters 
 
Parameters Functions 
Settings 
Factory 
Setting
Customer
 
11-00  V/F Curve Selection 
00: Determined by group 01 
01: 1.5 power curve 
02: 1.7 power curve 
03: 2 power curve 
04: 3 power curve 
00  
 
11-01  Circulative Control 
00: No function 
01: Time circulation (by time)
02: Fixed amount circulation 
(by PID) 
03: Fixed amount control (an 
AC drive runs with 4 
motors) 
00  
 
11-02  Multiple Motors Control 
01~04 
01 
 
 
11-03  Time Circulation Time Setting 
00~65500 Min 
00 
 
 
11-04  Motor Switch Delay Time 
0.0~3600.0 sec 
1.0 
 
 
11-05  Motor Switch Delay Time during 
Fixed Amount Circulation 
0.0~3600.0 sec 
10.0 
 
 
11-06  Motor Switch Frequency during 
Fixed Amount Circulation 
0.00 to 120.00 Hz 
60.00 
 
 
11-07  Enter Sleep Process Time 
0.0~3600.0sec 
0.0: Sleep function disable 
0.0  
 
11-08  Sleep Frequency of Sleep 
Process 
0.00 to 11-09   
(Wake up Frequency) 
0.0  
 
11-09  Wake Up Frequency of Sleep 
Process 
0.00 to 120.0Hz 
0.0 
 
 11-10 Treatment 
of 
Fixed 
Amount 
Circulation Malfunction 
00: Turn off all motors 
01: Turn off AC drive 
00  
 
11-11  Stop Frequency of Auxiliary 
Motor 