Chapter 6  Control Modes of Operation|ASDA-AB Series 
Revision March 2008, Doc. Name: 2007PDD23000011 
 
 
6-31 
For example, in torque mode, if P1-41 is set to 100 and the input voltage is 10V, it indicates that 
the torque command is 100% rated torque. If P1-41 is set to 100, but the input voltage is 
changed to 5V, then the torque command is changed to 50% rated torque. 
Torque command / limit = Input voltage x setting/10 (%) 
 
6.4.5  Timing Chart of Torque Control Mode 
T4 (P1-14)
T3 (P1-13)
T2 (P1-12)
T1
TCM0
TCM1
SON
OFF
ON
OFF
ON
ON
OFF
ON
Internal speed
command
External analog
voltage or zero (0) 
External I/O signal
 
NOTE
 
1)  OFF indicates normally open and ON indicates normally closed. 
2)  When torque control mode is Tz, the torque command T1=0; when torque control mode is T, the 
speed command T1 is external analog voltage input (Please refer to P1-01). 
3)  After Servo ON, the users can select command according to the state of TCM0~1.