 Chapter 7 Servo Parameters|ASDA-AB Series 
Revision March 2008, Doc. Name: 2007PDD23000011 
 
7-51
 
Group 2: P2-xx  Extension Parameters 
P2 - 00 
  KPP 
Proportional Position Loop Gain 
Communication Addr.: 0200H
Default: 35 
Related Section: 
Applicable Control Mode: Pt, Pr 
Section 6.2.8 
Unit: rad/s 
Range: 0 ~ 1023 
Settings: 
This parameter is used to set the position loop gain. It can increase stiffness, expedite position 
loop response and reduce position error. However, if the setting value is over high, it may 
generate vibration or noise.  
 
P2 - 01 
  PPR 
Position Loop Gain Switching Rate 
Communication Addr.: 0201H
Default: 100 
Related Section: N/A 
Applicable Control Mode: Pt, Pr 
 
Unit: % 
Range: 10 ~ 500 
Settings: 
This parameter is used to set the position gain switching rate when the gain switching condition 
is satisfied. Please refer to P2-27 for gain switching control selection settings and refer to P2-29 
for gain switching condition settings. 
 
P2 - 02 
  PFG 
Position Feed Forward Gain 
Communication Addr.: 0202H
Default: 5000 
Related Section: 
Applicable Control Mode: Pt, Pr 
Section 6.2.8 
Unit: 0.0001 
Range: 10 ~ 20000 
Settings: 
This parameter is used to set the feed forward gain when executing position control command. 
When using position smooth command, increase gain can improve position track deviation. 
When not using position smooth command, decrease gain can improve the resonance condition 
of mechanical system. However, if the setting value is over high, it may generate vibration or 
noise.