Chapter 12  Application Examples |ASDA-AB Series 
Revision March 2008, Doc. Name: 2007PDD23000011 
 
 
12-9 
12.4  Connecting to Delta TP04 Series 
Delta servo drives can be connected to Delta TP04 Series Operation Interface Panel and provide functions 
including: Home, JOG operation, Position learning function, Relative position control, Absolute position 
control, Monitor and parameter settings. 
 
Parameters Setting 
„
 
P1-01=1 (Position control (Pr) mode setting) 
„
 
P1-47=202 (SHOM drive ORGP to perform forward homing) 
„
 
P2-15=124 (Home detection position, contact: DI6) 
„
 
P2-16=127 (Activate signal of home, contact: DI7)  
„
 
P2-10=101 (Servo On (SON), default: DI1)  
„
 
P2-11=108 (Command triggered (CTRG), default: DI2)  
„
 
P2-12=111 (Position command selection (POS0), default: DI3)  
„
 
P2-13=112 (Position command selection (POS1), default: DI4)  
„
 
P3-02=1 (Communication protocol 7,E,1) 
„
 
P3-05=2 (RS-485 serial communication) 
Operation  
„
 
Re-start the power to be ON again. 
„
 
After Servo ready is completed, press the Servo ON key and activate the drive to be Servo ON.